Project Description
These cable terminations are suitable to be installed on single-stranded cables and are used in indoor spaces where they have no direct contact with wind, rain or snow.
This type of cable termination can be supplied at a voltage range from 3.3 to 36 kV.
- Room temperature ranging from -40 to +105 °C
- Cross-linked insulation
- Flame retardant
- Easy installation
- In accordance with CENELEC HD 629.1S1, DIN VDE 0278, IEC60502-4 Standard
- With UV protection layer
- With unlimited lifetime / energized as soon as it is installed on the cable
To order a cable with specific cross section and conductor type, you can act as follows at the time selecting the code.
For instance:
Indoor single core cable termination for a voltage of 24kv with 185 mm2 cross section and PHSK – 1I24 – 185BI bimetal cable lug
- Insulating tubing
- Stress control tubing
- Yellow tape
- Red tape
- Medium voltage cable lug
- Earth cable lug
- Installation manual
- Rain shed (needed for voltage of 24 kV or above)
- Armor kit (if the cable is armored)
- Earth kit (if the earth is tape shield)
- Angle boot (if needed based on the specifications of the electrical panel)
PHSK – 1I cable terminations are generally used in electrical substations, cities, factories and electrical panels which have suitable spaces or in electrical transformer rooms or indoor substations.
X = cable cross-section (mm2) Y= (A1/Cu/BI) Type of cable lug |
Length (mm) (H) | Cable cross-section (mm2) | Code | Uo (kV) |
Un (kV) |
Um (kV) |
210 | 6 – 1200 | HSK – 1I03 – XY | 1.9 | 3 | 3.3 |
210 | 6 – 1200 | HSK – 1I07 – XY | 3.3 | 6 | 7.2 |
270 | 10 – 1200 | HSK – 1I12 – XY | 6 | 10 | 12 |
330 | 10 – 1200 | HSK – 1I17 – XY | 7.2 | 11 | 17.5 |
330 | 10 – 1200 | HSK – 1I24 – XY | 12 | 20 | 24 |
430 | 10 – 1200 | HSK – 1I36 – XY | 19 | 33 | 36 |