Project Description
These joints are suitable to be installed on various types of single-stranded cables. Due to the significance of energy supply in these industries, the technology of these joints is in a way that they would be able to work difficult conditions of voltage and the likelihood of any problem in the joint has decreased to a large degree. They have also tolerance towards severe, abnormal and consecutive blows given the conditions of electromotors.
In environments with normal level of soil pollution and humidity, PHJCG – 11 joint is used for armored cables and PHJMG – 11 joint is used for non-armored cables.
For environments with high level of acidic or basic pollution in the soil or humidity or environments that are sunk in water, PHJEG – 11 joint is used for armored cables and PHJRG – 11 joint is used for non-armored cables.
- Insulating tubing
- Stress control tubing
- Yellow tape
- Semi-conductor tape
- Insulating tape
- Copper mesh
- Two-layer tubing (red / black)
- Medium voltage ferrule
- Earth ferrule
- Installation manual
- Taped jacketing tubing
- Earth kit (if the earth is tape shield)
- Resin case (for PHJRG – 11, PHJEG – 11 codes)
- Resin and hardener (for PHJRG – 11, PHJEG – 11 codes)
- Armor case (for PHJCG – 11 code)
- Room temperature ranging from -40 to +105 °C
- Cross-linked polymer insulation
- Flame retardant
- Easy installation
- In accordance with DIN VDE 0278, CENELEC HD 629.1S1, IEC60502-4 Standard
- With UV protection layer
- With unlimited lifetime / energized as soon as it is installed on the cable
To order for a cable with specific cross section and conductor type, you can act as follows at the time selecting the code.
For instance:
Single core joint with a voltage of 12kv and 300 mm2 cross section and copper ferrule and armored cable for an environment with normal humidity PHJMC – 1112 – 300 CU
X = cable cross-section (mm2)
Y= (CU/ AL /BI) Type of ferrule
Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries without Armor and an Environment with Normal Pollution HJMG-11
Cable cross-section (mm2) | Code | Uo (kV) |
Un (kV) |
Um (kV) |
6 – 1200 | HJMG – 1103 – XY | 1.9 | 3 | 3.3 |
6 – 1200 | HJMG – 1107 – XY | 3.3 | 6 | 7.2 |
10 – 1200 | HJMG – 1112 – XY | 6 | 10 | 12 |
10 – 1200 | HJMG – 1117 – XY | 8 | 15 | 17.5 |
10 – 1200 | HJMG – 1124 – XY | 12 | 20 | 24 |
10 – 1200 | HJMG – 1136 – XY | 19 | 33 | 36 |
Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries with Armor and an Environment with Normal Pollution HJCG-11
Cable cross-section (mm2) | Code | Uo (kV) |
Un (kV) |
Um (kV) |
6 – 1200 | HJCG – 1103 – XY | 1.9 | 3 | 3.3 |
6 – 1200 | HJCG – 1107 – XY | 3.3 | 6 | 7.2 |
10 – 1200 | HJCG – 1112 – XY | 6 | 10 | 12 |
10 – 1200 | HJCG – 1117 – XY | 8 | 15 | 17.5 |
10 – 1200 | HJCG – 1124 – XY | 12 | 20 | 24 |
10 – 1200 | HJCG – 1136 – XY | 19 | 33 | 36 |
Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries without Armor and an Environment with High Level of Pollution HJRG-11
Cable cross-section (mm2) | Code | Uo (kV) |
Un (kV) |
Um (kV) |
6 – 1200 | HJRG – 1103 – XY | 1.9 | 3 | 3.3 |
6 – 1200 | HJRG – 1107 – XY | 3.3 | 6 | 7.2 |
10 – 1200 | HJRG – 1112 – XY | 6 | 10 | 12 |
10 – 1200 | HJRG – 1117 – XY | 8 | 15 | 17.5 |
10 – 1200 | HJRG – 1124 – XY | 12 | 20 | 24 |
10 – 1200 | HJRG – 1136 – XY | 19 | 33 | 36 |
Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries with Armor and an Environment with High Level of Pollution HJEG-11
Cable cross-section (mm2) | Code | Uo (kV) |
Un (kV) |
Um (kV) |
6 – 1200 | HJEG – 1103 – XY | 1.9 | 3 | 3.3 |
6 – 1200 | HJEG – 1107 – XY | 3.3 | 6 | 7.2 |
10 – 1200 | HJEG – 1112 – XY | 6 | 10 | 12 |
10 – 1200 | HJEG – 1117 – XY | 8 | 15 | 17.5 |
10 – 1200 | HJEG – 1124 – XY | 12 | 20 | 24 |
10 – 1200 | HJEG – 1136 – XY | 19 | 33 | 36 |