Project Description

These joints are suitable to be installed on various types of three-stranded cables. Due to the significance of energy supply in these industries, the technology of these joints is in a way that they would be able to work difficult conditions of voltage and the likelihood of any problem in the joint has decreased to a large degree. They have also tolerance towards severe, abnormal and consecutive blows given the conditions of electromotors.

In environments with normal level of soil pollution and humidity, PHJCG-33 joint is used for armored cables and PHJMG-11 joint is used for non-armored cables.

For environments with high level of acidic or basic pollution in the soil or humidity or environments that are sunk in water, PHJEG-33 joint is used for armored cables and PHJRG-33 joint is used for non-armored cables.

  • Insulating tubing
  • Stress control tubing
  • Yellow tape
  • Semi-conductor tape
  • Insulating tape
  • Copper mesh
  • Two-layer tubing (red / black)
  • Medium voltage ferrule
  • Earth ferrule
  • Installation manual
  • Taped jacketing tubing
  • Earth kit (if the earth is tape shield)
  • Resin case (for PHJRG-33, PHJEG-33 codes)
  • Resin and hardener (for PHJRG-33, PHJEG-33 codes)
  • Armor case (for PHJCG-33 code)
  • Room temperature ranging from -40 to +105 °C
  • Cross-linked polymer insulation
  • Flame retardant
  • Easy installation
  • In accordance with DIN VDE 0278, CENELEC HD 629.1S1, IEC60502-4 Standard
  • With UV protection layer
  • With unlimited lifetime / energized as soon as it is installed on the cable

To order for a cable with specific cross section and conductor type, you can act as follows at the time selecting the code.

For instance:

Single core joint with a voltage of 36kv and 150 mm2 cross section and copper ferrule and non-armored cable for an environment with high level of humidity PHJRG – 150 CU

X = cable cross-section (mm2)
Y= (CU/ AL /BI) Type of ferrule

Heat Shrinkable Three Core Cable Joint for Oil, Gas and Petrochemical Industries without Armor and an Environment with Normal Pollution HJMG-33

Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
6 – 300 HJMG – 3303 – XY 1.9 3 3.3
6 – 300 HJMG – 3307 – XY 3.3 6 7.2
10 – 300 HJMG – 3312 – XY 6 10 12
10 – 300 HJMG – 3317 – XY 8 15 17.5
10 – 300 HJMG – 3324 – XY 12 20 24
10 – 300 HJMG – 3336 – XY 19 33 36

Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries with Armor and an Environment with Normal Pollution HJCG-33

Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
6 – 300 HJCG – 3303 – XY 1.9 3 3.3
6 – 300 HJCG – 3307 – XY 3.3 6 7.2
10 – 300 HJCG – 3312 – XY 6 10 12
10 – 300 HJCG – 3317 – XY 8 15 17.5
10 – 300 HJCG – 3324 – XY 12 20 24
10 – 300 HJCG – 3336 – XY 19 33 36

Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries without Armor and an Environment with High Level of Pollution HJRG-33

Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
6 – 300 HJRG – 3303 – XY 1.9 3 3.3
6 – 300 HJRG – 3307 – XY 3.3 6 7.2
10 – 300 HJRG – 3312 – XY 6 10 12
10 – 300 HJRG – 3317 – XY 8 15 17.5
10 – 300 HJRG – 3324 – XY 12 20 24
10 – 300 HJRG – 3336 – XY 19 33 36

Heat Shrinkable Single Core Cable Joint for Oil, Gas and Petrochemical Industries with Armor and an Environment with High Level of Pollution HJEG-33

Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
6 – 300 HJEG – 3303 – XY 1.9 3 3.3
6 – 300 HJEG – 3307 – XY 3.3 6 7.2
10 – 300 HJEG – 3312 – XY 6 10 12
10 – 300 HJEG – 3317 – XY 8 15 17.5
10 – 300 HJEG – 3324 – XY 12 20 24
10 – 300 HJEG – 3336 – XY 19 33 36