Project Description

These cable terminations are suitable to be installed on three-stranded cables and are used in indoor spaces where they have no direct contact with wind, rain or snow.

Due to the significance of energy supply in oil, gas and petrochemical industries, these cable terminations have been designed in a way that they would tolerate very difficult conditions such as voltage tensions with maximum power. Given the environmental conditions such as pollution and extreme heat and soil pollutants, the raw materials of these cable terminations have been manufactured in a way that they would be able to tolerate the above conditions, leading to a remarkable decrease in the likelihood of causing any problem.

  • Room temperature ranging from -40 to +105 °C
  • Cross-linked polymer insulation
  • Flame retardant
  • Easy installation
  • In accordance with CENELEC HD 629.1S1, DIN VDE 0278, IEC60502-4 Standard
  • With UV protection layer
  • With unlimited lifetime / energized as soon as it is installed on the cable
  • With great tolerance towards impulse voltage, voltage tensions and difficult environmental conditions
  • Insulating tubing
  • Stress control tubing
  • Yellow tape
  • Red tape
  • Medium voltage cable lug
  • Earth cable lug
  • Installation manual
  • Rain shed (needed for 24 kV and higher voltages)
  • Armor kit (if the cable is armored)
  • Earth kit (if the earth is tape shield)
  • Lead kit (if the cable is lead)
  • Angle boot (if needed based on the specifications of the electrical panel)
  • Cable breakout

PHSG – 3I cable terminations are mostly used in indoor electrical substations and electrical panels in oil, gas and petrochemical companies with standard spaces.

PHCG – 3I cable terminations too are like the above cable terminations with the difference that they are designed for installation in electrical panels with small space such as electromotor junction box.

X = cable cross-section (mm2)
Y= (A1/Cu/BI) Type of cable lug

Heat Shrinkable Indoor Three Core Cable Termination for Oil, Gas and Petrochemical Industries HSG – 3I

Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
400 6 – 400 HSG – 3I 03 – XY 1.9 3 3.3
400 6 – 400 HSG – 3I 07 – XY 3.3 6 7.2
450 10 – 400 HSG – 3I 12 – XY 6 10 12
500 10 – 400 HSG – 3I 17 – XY 7.2 11 17.5
600 10 – 400 HSG – 3I 24 – XY 12 20 24
750 10 – 400 HSG – 3I 36 – XY 19 33 36

Heat Shrinkable Indoor Three Core Cable Termination for Oil, Gas and Petrochemical Industries with Smaller Dimensions HCG – 3I

Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
350 6 – 400 HCG – 3I 03 – XY 1.9 3 3.3
350 6 – 400 HCG – 3I 07 – XY 3.3 6 7.2
380 10 – 400 HCG – 3I 12 – XY 6 10 12
420 10 – 400 HCG – 3I 17 – XY 7.2 11 17.5
520 10 – 400 HCG – 3I 24 – XY 12 20 24
650 10 – 400 HCG – 3I 36 – XY 19 33 36