Project Description

These cable terminations are suitable to be installed on single-stranded cables and are used in indoor spaces where they have no direct contact with wind, rain or snow.

Due to the significance of energy supply in oil, gas and petrochemical industries, these cable terminations have been designed in a way that they would tolerate very difficult conditions such as voltage tensions with maximum power. Given the environmental conditions such as pollution and extreme heat and soil pollutants, the raw materials of these cable terminations have been manufactured in a way that they would be able to tolerate the above conditions, leading to a remarkable decrease in the likelihood of causing any problem.

  • Room temperature ranging from -40 to +105 °C
  • Cross-linked polymer insulation
  • Flame retardant
  • Easy installation
  • In accordance with CENELEC HD 629.1S1, DIN VDE 0278, IEC60502-4 Standard
  • With UV protection layer
  • With unlimited lifetime / energized as soon as it is installed on the cable
  • With great tolerance towards impulse voltage, voltage tensions and difficult environmental conditions
  • Insulating tubing
  • Stress control tubing
  • Yellow tape
  • Red tape
  • Medium voltage cable lug
  • Earth cable lug
  • Installation manual
  • Rain shed (needed for 24 kV and higher voltages)
  • Armor kit (if the cable is armored)
  • Earth kit (if the earth is tape shield)
  • Angle boot (if needed based on the specifications of the electrical panel)

PHSG – 1I cable terminations are mostly used in indoor electrical substations and electrical panels in oil, gas and petrochemical companies with standard spaces. PHCG – 1I cable termination too is like the above cable terminations with the difference that they are designed for installation in electrical panels with small space such as electromotor junction box.

X = cable cross-section (mm2)
Y= (A1/Cu/BI) Type of cable lug

Heat Shrinkable Indoor Single Core Cable Termination for Oil, Gas and Petrochemical Industries HSG – 1I

Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
210 6 – 1200 HSG – 1I 03 – XY 1.9 3 3.3
210 6 – 1200 HSG – 1I 07 – XY 3.3 6 7.2
270 10 – 1200 HSG – 1I 12 – XY 6 10 12
330 10 – 1200 HSG – 1I 17 – XY 7.2 11 17.5
330 10 – 1200 HSG – 1I 24 – XY 12 20 24
430 10 – 1200 HSG – 1I 36 – XY 19 33 36

Heat Shrinkable Indoor Single Core Cable Termination for Oil, Gas and Petrochemical Industries with Smaller Dimensions HCG – 1I

Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
170 6 – 1200 HCG – 1I 03 – XY 1.9 3 3.3
170 6 – 1200 HCG – 1I 07 – XY 3.3 6 7.2
200 10 – 1200 HCG – 1I 12 – XY 6 10 12
220 10 – 1200 HCG – 1I 17 – XY 7.2 11 17.5
220 10 – 1200 HCG – 1I 24 – XY 12 20 24
370 10 – 1200 HCG – 1I 36 – XY 19 33 36