Project Description

These cable terminations are suitable to be installed on single-stranded cables and are used in outdoor spaces where they have direct contact with wind, rain or snow and where there is mild pollution in the environment.
This type of cable termination can be supplied at a voltage range from 3.3 to 36 kV.

  • Room temperature ranging from -40 to +105 °C
  • Cross-linked insulation
  • Flame retardant
  • Easy installation
  • In accordance with CENELEC HD 629.1S1, DIN VDE 0278, IEC60502-4 Standard
  • With UV protection later
  • With unlimited lifetime / energized as soon as it is installed on the cable

To order a cable with specific cross section and conductor type, you can act as follows at the time selecting the code.

For instance:

Outdoor single core cable termination for a voltage of 24kv with 185 mm2 cross section and PHSK – 1E24 – 185AI aluminum cable lug

  • Insulating tubing
  • Stress control tubing
  • Yellow tape
  • Red tape
  • Medium voltage cable lug
  • Earth cable lug
  • Installation manual
  • Rain shed (needed for voltage of 24 kV or above)
  • Armor kit (if the cable is armored)
  • Earth kit (if the earth is tape shield)

PHSK – 1E cable terminations are generally used in electrical substations, cities, factories and electrical panels and also in some platforms or transmission tower which have suitable spaces for installation.

X = cable cross-section (mm2)
Y= (A1/Cu/BI) Type of cable lug
Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
260 6 – 1200 HSK – 1E03 – XY 1.9 3 3.3
260 6 – 1200 HSK – 1E07 – XY 3.3 6 7.2
360 10 – 1200 HSK – 1E12 – XY 6 10 12
410 10 – 1200 HSK – 1E17 – XY 7.2 11 17.5
410 10 – 1200 HSK – 1E24 – XY 12 20 24
560 10 – 1200 HSK – 1E36 – XY 19 33 36