Project Description

These cable terminations are suitable to be installed on single-stranded cables and are used in indoor spaces where they have no direct contact with wind, rain or snow.
This type of cable termination can be supplied at a voltage range from 3.3 to 36 kV.

  • Room temperature ranging from -40 to +105 °C
  • Cross-linked insulation
  • Flame retardant
  • Easy installation
  • In accordance with CENELEC HD 629.1S1, DIN VDE 0278, IEC60502-4 Standard
  • With UV protection layer
  • With unlimited lifetime / energized as soon as it is installed on the cable

 

To order a cable with specific cross section and conductor type, you can act as follows at the time selecting the code.

For instance:

Indoor single core cable termination for a voltage of 24kv with 185 mm2 cross section and PHSK – 1I24 – 185BI bimetal cable lug

  • Insulating tubing
  • Stress control tubing
  • Yellow tape
  • Red tape
  • Medium voltage cable lug
  • Earth cable lug
  • Installation manual
  • Rain shed (needed for voltage of 24 kV or above)
  • Armor kit (if the cable is armored)
  • Earth kit (if the earth is tape shield)
  • Angle boot (if needed based on the specifications of the electrical panel)
PHSK – 1I cable terminations are generally used in electrical substations, cities, factories and electrical panels which have suitable spaces or in electrical transformer rooms or indoor substations.
X = cable cross-section (mm2)
Y= (A1/Cu/BI) Type of cable lug
Length (mm) (H) Cable cross-section (mm2) Code Uo
(kV)
Un
(kV)
Um
(kV)
210 6 – 1200 HSK – 1I03 – XY 1.9 3 3.3
210 6 – 1200 HSK – 1I07 – XY 3.3 6 7.2
270 10 – 1200 HSK – 1I12 – XY 6 10 12
330 10 – 1200 HSK – 1I17 – XY 7.2 11 17.5
330 10 – 1200 HSK – 1I24 – XY 12 20 24
430 10 – 1200 HSK – 1I36 – XY 19 33 36